Intermediate Guide

RCD Protection Zones Explained: How to Design a Modern Consumer Unit

📅 ✍️ ElectraSim ⏱ 15 min read

Fitting an RCD to a consumer unit sounds straightforward. In practice, how you zone that protection — which circuits share an RCD, which have individual RCBOs, and how the devices coordinate under fault conditions — determines whether an installation is merely compliant or genuinely well-designed.

Get the zoning wrong and a faulty garden lamp trips the fridge at 2 am. Get it right and a fault on any single circuit trips only that circuit, leaving every other load unaffected.

This guide explains the four main protection architectures used in UK domestic consumer units, how to assign circuits to zones, how RCD discrimination works, and what the current wiring regulations (BS 7671 18th Edition, Amendment 2) actually mandate.

💡 Simulate it: ElectraSim includes Distribution Board, MCB, RCD, and RCBO components. Build a split-load or fully-RCBO consumer unit layout and test fault isolation before touching any real wiring. Open ElectraSim →


Why Protection Zoning Matters

An RCD does not care which circuit caused the fault. If circuits A, B, C, and D all share one 30 mA RCD, a fault on circuit D trips the RCD — and circuits A, B, and C lose power simultaneously.

In most homes this is an inconvenience. In some situations it is a safety hazard:

Protection zoning is the discipline of deciding which circuits share which protective device, so that a fault causes the minimum necessary interruption while still meeting all regulatory requirements.


The Four Consumer Unit Architectures

1. Single Whole-Board RCD (Largely Obsolete)

Main Switch

RCD (30 mA) — covers ALL circuits
    ├── MCB → Lighting 1
    ├── MCB → Lighting 2
    ├── MCB → Ring Main
    ├── MCB → Kitchen
    ├── MCB → Shower
    └── MCB → Outdoor

One RCD protects every circuit in the installation. A fault anywhere trips everything.

Advantages: cheap, simple, maximum coverage.

Disadvantages:

Status: found in older installations. Acceptable as existing, but should not be specified for new work.


2. Split-Load Consumer Unit (Common in UK Domestic, 2000s–2020s)

Main Switch
    ├── RCD-1 (30 mA)              ├── No RCD (unprotected side)
    │     ├── MCB → Lighting 1     │     ├── MCB → Fridge/Freezer
    │     ├── MCB → Ring Main      │     ├── MCB → Alarm / Smoke detectors
    │     ├── MCB → Kitchen        │     └── MCB → (any circuit where loss
    │     ├── MCB → Bathroom            of power during a trip is critical)
    │     └── MCB → Outdoor

The consumer unit is divided into two sections by the main switch. One section is behind an RCD; the other is not.

The logic: circuits on the unprotected side are ones where:

  1. The appliance is unlikely to cause an earth fault (static appliances with fixed wiring), or
  2. Losing power during a fault elsewhere would be unacceptable

Advantages: preserves power to critical loads during a fault trip; reduces the scope of a nuisance trip.

Disadvantages:

Status: still widely found and fully functional as existing. Not recommended for new domestic installations where individual RCBO protection is practical.


3. Dual-RCD Split-Load (Two Protected Zones)

Main Switch
    ├── RCD-1 (30 mA)              ├── RCD-2 (30 mA)
    │     ├── MCB → Lighting 1     │     ├── MCB → Lighting 2
    │     ├── MCB → Ring Main      │     ├── MCB → Kitchen
    │     └── MCB → Shower         │     ├── MCB → Outdoor
    │                              │     └── MCB → Garage

Two RCDs divide the circuits into two zones. A fault on any circuit in Zone 1 affects only Zone 1; Zone 2 remains live.

Advantages: better resilience than single-RCD — a nuisance trip affects half the circuits, not all of them.

Disadvantages:

Circuit allocation best practice for dual-RCD:


4. Fully RCBO-Protected (Current Best Practice)

Main Switch
    ├── RCBO → Lighting 1      (6 A / 30 mA Type A)
    ├── RCBO → Lighting 2      (6 A / 30 mA Type A)
    ├── RCBO → Ring Main       (32 A / 30 mA Type A)
    ├── RCBO → Kitchen         (32 A / 30 mA Type A)
    ├── RCBO → Shower          (40 A / 30 mA Type A)
    ├── RCBO → Immersion       (16 A / 30 mA Type A)
    ├── RCBO → Outdoor         (16 A / 30 mA Type A)
    ├── RCBO → Garage/Shed     (16 A / 30 mA Type A)
    ├── RCBO → EV Charger      (32 A / 30 mA Type B)
    └── RCBO → Cooker          (32 A / 30 mA Type A)

Every circuit has its own RCBO — a combined MCB + RCD. A fault on any single circuit trips only that RCBO. Every other circuit is unaffected and independently protected.

Advantages:

Disadvantages:

Status: the current recommended standard for all new domestic installations in the UK. Most competent electricians now default to this layout.


RCD Type Selection: AC, A, F, and B

Selecting the wrong RCD type is a common and consequential mistake. The type defines which waveforms of fault current the device can detect:

TypeDetectsRequired For
Type ACSinusoidal AC earth faults onlyTraditional resistive loads (heating elements, incandescent lamps)
Type AAC + pulsating DC earth faultsWashing machines, dishwashers, modern switch-mode PSUs, single-phase EV chargers without internal DC fault detection
Type FType A + high-frequency fault currentsVariable-speed drives, inverter-driven heat pumps
Type BAll of the above + smooth DCThree-phase EV chargers, some solar inverters, certain medical equipment

The practical rule for domestic installations:

A Type AC RCBO will not detect DC earth fault currents. As virtually every modern appliance contains switched-mode power electronics that can produce pulsating DC fault currents, fitting Type AC RCDs in new domestic installations is no longer best practice — even if technically permitted in some legacy guidance.


RCD Discrimination: Upstream vs Downstream

When an installation has more than one level of RCD protection — for example, a 100 mA RCD at the origin feeding circuits with 30 mA RCDs or RCBOs downstream — the devices must discriminate: a fault downstream should trip the downstream RCD, not the upstream one.

Why Discrimination Matters

If a 30 mA earth fault on a socket outlet trips the main incoming 100 mA RCD instead of the socket circuit’s RCBO, you have no selectivity — the entire installation loses power for a fault on one socket.

How to Achieve Discrimination

Discrimination between two RCDs in series is achieved by:

  1. Current ratio: the upstream RCD must have a higher rated residual operating current than the downstream RCD. A 100 mA upstream device discriminates with 30 mA downstream devices. A 30 mA upstream device cannot discriminate with another 30 mA downstream device.

  2. Time delay: the upstream device is a time-delayed (S-type) RCD — it deliberately delays tripping by 60–200 ms, allowing downstream instantaneous devices to clear the fault first. S-type RCDs are used at the origin of commercial and industrial installations.

  3. Both: using both current ratio and time delay gives the highest reliability.

For domestic split-load and RCBO installations:

Discrimination becomes critical when a TT earthing system is used (common for rural properties, outbuildings, and agricultural premises), where a high-current RCD at the origin is typically fitted alongside 30 mA RCDs at individual circuits.


BS 7671 18th Edition: What the Regulations Actually Require

The 18th Edition of the IET Wiring Regulations (BS 7671:2018, including Amendment 2:2022) significantly expanded RCD requirements compared to the 17th Edition. Key mandatory requirements for new domestic installations:

Regulation 411.3.4 — Socket Outlets

All socket outlets rated up to 32 A in domestic premises must have 30 mA RCD protection unless the socket is specifically for a named appliance that is unlikely to be used outdoors or in a high-risk location. This effectively means all domestic socket circuits must be RCD-protected.

Regulation 522.6.7 — Cables in Walls

Any cable buried in a wall or partition at less than 50 mm depth that is not enclosed in earthed metallic conduit must have 30 mA RCD protection. This catches the vast majority of domestic cable runs — most cables are within 50 mm of the surface.

Regulation 701 — Bathroom Zones

All circuits in a bathroom must have 30 mA RCD protection. There are no exceptions for fixed heating or lighting — everything in zones 0, 1, 2, and the outer zone must be RCD-protected.

Regulation 709 — Marina/Outdoor — not domestic, but…

For outbuildings and garden circuits, 30 mA protection is mandatory.

Amendment 2 — SPD Requirement

Amendment 2 (2022) introduced a requirement to consider Surge Protection Devices (SPDs) for all new domestic installations. Where the installation is supplied via overhead cables (exposed to lightning) or the risk of surge damage is significant, an SPD at the origin is now expected. This does not change RCD zoning but is increasingly seen alongside it in new consumer units.

In practice: for any new consumer unit installation or rewire in the UK, fitting individual RCBOs on every circuit is the most straightforward way to satisfy all of Regulation 411.3.4 and 522.6.7 without needing to audit which circuits require RCD protection and which do not.


Planning a Consumer Unit Layout: Step-by-Step

Here is a practical approach to allocating circuits to protection zones for a typical 3-bedroom UK home:

Step 1: List All Circuits

Start by listing every circuit the installation needs:

CircuitLoadTypical MCBNotes
Upstairs lighting0.5–1 kW6 A
Downstairs lighting0.5–1 kW6 A
Ring main — upstairsUp to 7.2 kW32 A
Ring main — downstairsUp to 7.2 kW32 A
Kitchen socketsUp to 7.2 kW32 AHigh use
Cooker / hob5–12 kW32–45 ADedicated radial
Shower7–10.5 kW40–45 ADedicated radial
Immersion heater3 kW16 ADedicated radial
Bathroom shaver socket<0.1 kW6 AZone 2, shaver transformer
Outdoor socketsUp to 3.5 kW16–32 AMust be RCD protected
Garage / shedUp to 3.5 kW16–32 ASub-board optional
EV charger3.7–7.4 kW32–40 AType B RCBO
Smoke detectors<0.1 kW6 AConsider uninterruptible supply

Step 2: Identify Critical Circuits

Circuits where power loss is unacceptable or safety-critical:

For these circuits in a split-load design, place them on a separate zone or the unprotected side. In a fully RCBO design, each is independently protected — no special allocation needed.

Step 3: Identify High-Risk Circuits

Circuits with higher earth fault probability:

Ensure these are behind a 30 mA RCD (RCBO or shared RCD).

Step 4: Match RCBO Types to Circuits

CircuitRCBO Type
Lighting, immersion, cookerType A
All socket circuitsType A
EV charger (single-phase, no internal DC protection)Type A or B — check charger manual
EV charger (three-phase)Type B
Solar inverter circuitCheck inverter documentation — may need Type B
Heat pump (inverter-driven)Type F or Type A — check equipment manual

Step 5: Choose Consumer Unit Size

Always fit one size larger than current need. A 3-bedroom house with the circuits above needs approximately 12–14 ways. Fit an 18-way board to allow for future EV charger, solar, or additional circuits without replacing the consumer unit.


Common Mistakes in RCD Protection Zoning

Putting the Fridge and Freezer on the Same RCD Zone

If both are behind RCD-1 and a fault trips RCD-1, all cold food storage is lost. Split the fridge and freezer across different zones — or use individual RCBOs.

Using Type AC RCDs in Modern Installations

Type AC does not detect pulsating DC fault currents, which modern electronics routinely produce. Fitting Type AC in a new installation is increasingly poor practice even where it remains technically permissible.

Concentrating All High-Risk Circuits on One RCD

If bathroom, kitchen, outdoor, and garage circuits are all behind RCD-1, a single fault in any of them trips all of them. Spread high-risk circuits across zones — or use individual RCBOs.

Ignoring Discrimination in TT Installations

In a TT system (earth electrode, common in rural properties), a main incoming RCD combined with 30 mA downstream RCDs needs proper discrimination. If the main RCD is also 30 mA with no time delay, both may attempt to trip simultaneously. The main RCD should be 100 mA time-delayed (S-type), or the downstream devices should be 30 mA instantaneous.

Overloading One RCD Zone

If every high-consumption circuit (shower, cooker, EV charger, immersion) sits behind the same RCD, cumulative cable leakage from many long circuits may cause nuisance tripping even without a real fault. In older cable with slightly degraded insulation, the combined leakage current across five large circuits can approach the 30 mA trip threshold. Distribution across two zones or individual RCBOs eliminates this.


How to Simulate RCD Zones in ElectraSim

ElectraSim lets you build and test consumer unit protection layouts directly in the browser — no installation or sign-up required.

Building a Split-Load Layout

  1. Open ElectraSim
  2. Place a Distribution Board — this represents your consumer unit busbars
  3. Add two RCD components downstream of the DB output — one for each zone
  4. Add MCB components downstream of each RCD, one per circuit
  5. Attach loads (bulbs, sockets, fan) to each MCB output
  6. Press Run — all circuits energise from the common DB supply
  7. Enable Fault Simulation (⚠ button) and apply an Earth Fault to a load on Zone 1
  8. Zone 1’s RCD trips; Zone 2 circuits remain live — exactly what a correctly zoned split-load installation should do

Building a Fully RCBO Layout

  1. Place a Distribution Board
  2. Place individual MCB and RCD pairs in series for each circuit (ElectraSim RCBO = MCB + RCD in series per circuit)
  3. Apply an earth fault to any single circuit
  4. Only that circuit’s RCD trips — all others remain live

This makes the fault isolation advantage of the RCBO layout immediately visible without touching any live equipment.


Key Takeaways

Build your consumer unit layout before you wire it: Open ElectraSim → and test every fault scenario safely.

See It All in Action

Build and simulate the circuits from this article for free in your browser. No installation, no sign-up.

⚡ Open ElectraSim Free