Wiring Guide

How to Add a Spur from a Ring Main: Rules, Methods and Step-by-Step Guide

📅 ✍️ ElectraSim ⏱ 13 min read

Adding a new socket outlet to an existing ring main by running a spur is one of the most common electrical tasks in UK homes. It avoids the disruption of re-running the entire ring and, within the limits set by BS 7671, is a perfectly compliant way to extend the number of socket outlets in a room.

This guide covers what a spur is, the BS 7671 rules that govern them, how to find a valid take-off point, step-by-step wiring for both fused and unfused spurs, and when the work requires Part P notification.

You can model spur behaviour in ElectraSim before starting any physical work.


What Is a Spur?

A spur is a branch cable that runs from the ring final circuit to supply one or more additional outlets. Unlike the ring cable itself — which forms a closed loop back to the consumer unit — a spur has only one cable path. Current to a spur must travel entirely along that single branch cable.

This distinction matters because the ring’s overcurrent protection (the 32 A MCB or RCBO) is sized for a ring, where current splits across two paths. On a spur, the full load of that spur passes through a single 2.5 mm² cable — which is rated at 24 A clipped direct. A 32 A MCB cannot reliably protect a single 2.5 mm² cable against overload.

BS 7671 addresses this by strictly limiting what can be connected to an unfused spur.

Related: How to Wire a Ring Main Circuit: The UK Ring Final Circuit Explained


Two Types of Spur

Unfused spur

An unfused spur runs from the ring to a single socket outlet or connection point, with no additional fuse protection at the spur origin. The only overcurrent protection is the ring’s own MCB/RCBO.

BS 7671 rules for unfused spurs:

Fused spur (fused connection unit)

A fused spur uses a fused connection unit (FCU) at the point where the branch leaves the ring. The FCU contains a cartridge fuse — typically 13 A or lower — that provides additional overcurrent protection for the spur cable and anything downstream.

Because the FCU limits the maximum current in the spur to its fuse rating, the rules on what can be connected downstream are more flexible:

Related: How to Wire a Fused Connection Unit (FCU): Switched, Unswitched and Spur Rules


BS 7671 Spur Rules: Summary

RuleUnfused spurFused spur (FCU)
Max outlets at end of spur1 socket (single or double)1 fixed appliance or sub-circuit
Spur from a spurNot permittedNot permitted
Max spurs per ring≤ number of sockets on ringNo specific limit
Cable sizeSame as ring (2.5 mm²)Same as ring to FCU; smaller downstream if fuse allows
Additional protection at originNoneFCU fuse

The key principle: an unfused spur must never be able to carry more current than its cable can safely handle. A single socket outlet with a 13 A plug fuse limits the spur to 13 A — well within the capacity of 2.5 mm² cable. This is why one socket is permitted, but not two sockets in a double-gang box wired as separate outlets without fuse protection.


Finding a Valid Take-Off Point

You can branch a spur from three locations on the ring:

1. From an existing ring socket

The most common and accessible approach. A ring socket has two sets of conductors entering its back box (in and out of the ring). Adding a spur creates a third set.

How to confirm a socket is on the ring (not already a spur):

Open the back box and count the conductors:

This check is essential. Spurring from a spur violates BS 7671 and undermines the overcurrent protection of the circuit.

2. From a junction box on the ring cable

A 30 A three-terminal junction box can be inserted into the ring cable at any accessible point — in the floor void, ceiling, or surface trunking — to create a take-off point. The ring cable connects to two terminals; the spur cable connects to the third.

This is useful when you need to spur to a location that is not near an existing socket, or when the nearest socket already has a spur.

3. At the consumer unit

Technically, a spur can originate from the consumer unit terminals (the same terminals as the ring ends). However, this is rarely done in practice — it requires additional cable runs and uses consumer unit space. It is more appropriate to install a new radial circuit in this situation.


What You Need

For adding an unfused spur to a new single or double socket:


Step-by-Step: Unfused Spur from an Existing Ring Socket

Step 1: Isolate and verify dead

Turn off the MCB or RCBO protecting the ring circuit at the consumer unit. Lock it off or tape it if possible. Use a voltage tester on the existing socket to confirm it is dead. Do not rely on the MCB position alone.

Step 2: Open the take-off socket

Remove the socket faceplate and carefully withdraw the back box to confirm it is a ring socket (two cables entering — see above). If it has only one cable, choose a different socket.

Step 3: Route the new cable

Run 2.5 mm² twin and earth from the take-off socket to the location of the new socket. Common routes:

Leave 150–200 mm of cable at each end for connection.

Step 4: Connect at the new socket

At the new socket back box:

Fold conductors neatly and fit the faceplate. Do not over-tighten terminal screws — finger-tight plus a quarter turn is sufficient for most socket terminals.

Step 5: Connect at the take-off socket

At the existing ring socket, you now have three sets of conductors (two ring cables + one spur):

If the terminal cannot safely accept three conductors, fit a 30 A junction box behind the socket or in an accessible location nearby and connect the spur from the junction box instead.

Step 6: Test before energising

Before switching the MCB back on:

Switch the MCB on and test the new socket with a socket tester.


Step-by-Step: Fused Spur (FCU) for a Fixed Appliance

A fused connection unit is the correct way to connect a fixed appliance — a fridge, washing machine, boiler, extractor fan, or towel rail — without a plug and socket.

Step 1: Select the FCU

Step 2: Isolate and verify dead

Same as Step 1 above.

Step 3: Route cable from ring to FCU

Run 2.5 mm² twin and earth from the take-off socket (or junction box) to the FCU mounting position. The FCU should be positioned near the appliance and accessible — not buried behind it.

Step 4: Connect at the FCU

FCUs have two sets of terminals — Feed (supply in from ring) and Load (output to appliance):

Feed side (ring supply):

Load side (to appliance):

Step 5: Connect at the take-off point

Same as Step 5 of the unfused spur above — connect the spur cable at the ring socket or junction box.

Step 6: Test

Test continuity, polarity, and insulation resistance. Energise the circuit and confirm the FCU switch and indicator operate correctly.


Voltage Drop Check

For a short spur (up to 5 m), voltage drop is negligible. For longer runs:

Using 2.5 mm² twin and earth (mV/A/m = 18), a 10 m spur at 13 A:

V_drop = (18 × 13 × 10) / 1000 = 2.34 V

Well within the 5% limit (11.5 V). Even at 20 m, voltage drop on a 13 A spur is under 5 V — not a concern for domestic socket spurs.

Related: Voltage Drop Explained: How to Calculate It and Why It Matters


Part P Notification

Adding a spur in most locations is not notifiable under Part P — it is classified as an addition to an existing circuit, not a new circuit.

Exceptions — notifiable:

Not notifiable:

If in doubt, check with your local Building Control authority — notification is free and avoids future issues when selling the property.

Related: Part P Building Regulations Explained: What UK Homeowners Can and Can’t DIY


Simulating a Spur in ElectraSim

In ElectraSim, you can model the difference between a ring socket and a spur to understand the overcurrent protection implications:

  1. Build a ring circuit with a 32 A RCBO, several sockets on the ring, and a load at each
  2. Add a spur socket branching from one ring socket — add a load to the spur
  3. Run the simulation — observe that the spur load is fed by a single cable path, while ring sockets share two paths
  4. Increase the spur load until the single spur cable is overloaded — observe that the 32 A RCBO may not trip in time to protect the spur cable alone
  5. Add an FCU at the spur origin with a 13 A fuse — repeat the overload test and observe that the FCU fuse now provides the protection that the RCBO alone could not

This directly demonstrates why the spur rules exist — and why fused spurs are a safer choice for high-demand outlets.

Open ElectraSim — free, no sign-up →


Common Mistakes

MistakeRiskCorrect approach
Spurring from a spurOverload on first spur cable, non-compliantOnly spur from a confirmed ring socket or junction box on the ring
Not checking if socket is on ring or spurCascading spursCount cables in back box before connecting
Using 1.5 mm² cable for the spurCable overheats at 13 AUse 2.5 mm² throughout; 1.5 mm² only for lighting
Fitting two socket outlets at end of unfused spurEffectively doubles potential load without fuse protectionOne socket only; use FCU if multiple outlets needed
No earth sleeving on bare CPCExposed bare copper conductorAlways sleeve the CPC green/yellow before connecting
Three conductors forced into single terminalPoor connection, arcing riskUse junction box or Wago connectors if terminal is full
Not testing before re-energisingWiring fault goes live undetectedAlways test continuity and polarity before switching on

Key Points

See It All in Action

Build and simulate the circuits from this article for free in your browser. No installation, no sign-up.

⚡ Open ElectraSim Free