Electrical Safety

EICR Codes Explained: C1, C2, C3 and FI — What Each Code Means

📅 ✍️ ElectraSim ⏱ 20 min read

An EICR report arrives and the first thing you see is a list of observations — each followed by a code: C1, C2, C3, or FI. You know the codes indicate severity. But which ones make the report fail? What does each one actually mean in practice? And what does a C2 mean for a landlord with a 28-day deadline?

This guide explains every EICR code in depth, maps real-world faults to specific codes, shows what remedial work costs for each level, and covers the property-sale and insurance implications that most guides skip.

💡 Understand faults before they happen. ElectraSim lets you build circuits and inject the same faults an EICR inspector looks for — reverse polarity, missing earths, absent RCD protection — and see exactly how each affects the circuit. Open ElectraSim →


What Is an EICR and What Are the Codes?

An Electrical Installation Condition Report (EICR) is a formal document produced by a qualified electrician after inspecting and testing the fixed electrical installation in a property. Every observation is assigned a condition code indicating its severity.

The four codes are:

CodeShort nameSeverity
C1Danger PresentImmediate danger
C2Potentially DangerousCould become dangerous
C3Improvement RecommendedDoes not comply with current BS 7671
FIFurther Investigation RequiredCannot be fully assessed

A Satisfactory EICR means no C1 or C2 findings. An Unsatisfactory EICR means one or more C1 or C2 findings — remedial work is required before the installation can be re-tested and pass.


C1 — Danger Present

What it means

The installation has a defect that creates immediate risk of injury. The affected circuit or the entire installation should be isolated immediately — do not use it until the defect is corrected.

What faults produce a C1

FaultWhy it is C1Example scenario
Live conductors accessible without toolsDirect contact riskBroken socket faceplate exposing live terminals; missing cover on a junction box
No earth on a circuit feeding metal appliancesEarth fault would make the casing live with no path to trip protectionOld rubber cable feeding a metal light fitting with no CPC
Insulation failure with live conductor exposedDirect contact or fire riskCable crushed behind a screw in a wall, copper exposed
Evidence of arcing, burning, or severe overheatingActive fire / shock riskMelted terminal block, scorch marks around a socket, burning smell from a consumer unit
Reversed polarity where the switch breaks neutralLamp holder shell is live when the switch is offChanging a bulb kills power to the lamp but the holder is still at 230 V
Damaged cable insulation inside a wallHidden live conductor in contact with masonry or moistureDrill through a cable during renovation, insulation damaged but not shorted

What happens with C1

Typical remedial cost

C1 faultTypical cost
Replace damaged socket with correct polarity£50–£120
Repair or re-route damaged cable£100–£250
Replace burnt terminal block / connector£50–£150
Full rewire of affected circuit£400–£800

How to simulate in ElectraSim

  1. Place a Power Supply and Bulb in ElectraSim
  2. Wire the switch into the neutral path (reverse polarity)
  3. Toggle the switch off — the bulb goes dark but the live connection to the holder remains active
  4. This demonstrates exactly why C1 exists: the holder is live at 230 V even when the switch is off

C2 — Potentially Dangerous

What it means

The installation has a defect that is not immediately dangerous but could become dangerous under certain conditions. Remedial action is required — the EICR is Unsatisfactory.

What faults produce a C2

FaultWhy it is C2Example scenario
No RCD protection on socket circuitsEarth faults above 30 mA would not disconnect fast enough1980s MCB board with no RCDs
MCB rated too high for the cableCable can overheat without tripping the MCB10 A MCB protecting a 1.0 mm² lighting cable (rated 13.5 A but 10 A MCB is actually correct; this example is 16 A MCB on 1.0 mm² — the cable overheats)
Missing or inadequate earthingFault current has no path; MCB/RCBO cannot operateMissing earth conductor on a circuit feeding metal appliances
Bathroom wiring not in correct zoneWater contact risk with mains voltageIPX1 fitting installed inside Zone 1
Old rewirable fuse board with no RCDNo earth fault protection at all1970s porcelain fuse board still in service
Open ring circuitSingle cable leg carries full load; cable overheatsSocket removed without bridging the ring
No main bonding on gas or water pipesFault current path incomplete; touch voltage on pipeworkGas pipe not bonded in a property with a metal gas installation
Overloaded circuit exceeding cable capacitySustained heat degrades insulationKitchen ring running kettle, microwave, dishwasher, and air fryer simultaneously on a 32 A circuit

What happens with C2

Typical remedial cost

C2 faultTypical cost
Fit RCBOs to socket and bathroom circuits£200–£450
Consumer unit upgrade (old board → modern RCBO)£500–£900
Repair or extend main bonding£100–£250
Repair open ring (bridge the break)£80–£200
Replace cable that fails insulation resistance£150–£400 per circuit
Relocate bathroom fitting to correct zone£100–£300

📖 Related: Consumer Unit Upgrade: What to Expect When Replacing Your Fuse Board — a consumer unit upgrade is the most common C2 remedial work; this guide explains the full process and costs.

How to simulate in ElectraSim

  1. Build a circuit with a Power Supply, Switch, and Bulb
  2. Remove the earth connection from the circuit
  3. The circuit continues to operate normally — the missing earth is invisible in normal use
  4. Add an RCD and inject an earth fault — the RCD trips; without the RCD, the fault persists undetected
  5. This demonstrates why “no RCD protection” is a C2: the MCB does not detect earth leakage

What it means

The installation does not comply with the current edition of BS 7671, but it may have complied when originally installed. The defect is not dangerous and does not make the EICR Unsatisfactory — but improvement is recommended.

What faults produce a C3

FaultWhy it is C3 (not C2)Example scenario
Old fuse board with no RCDs — but no metal-clad appliances on those circuitsCompliant when installed; not compliant now1990s MCB board; all lighting circuits with plastic fittings only
Cables without correct colour sleevingCosmetic / identification issue; no safety impact if conductors are correctly connectedOld red/black cable without brown/blue sleeving at the consumer unit
No supplementary bonding in bathroom — where RCDs are presentRCD provides the protection that bonding would otherwise offerModern installation with RCBOs on all circuits; no supplementary bonding
Socket outlets without shuttered aperturesNon-compliant with current BS 7671 but no direct dangerOld-style unshuttered sockets in a room without children
Missing circuit labels on the consumer unitIdentification issue; not dangerous but makes future work harderConsumer unit with blank or illegible labels
No fire-rated downlight coversFire spread risk under certain conditions but not electrical dangerDownlights installed without fire-rated IC covers

What happens with C3

Typical remedial cost

C3 faultTypical cost
Add circuit labels to consumer unit£0–£30 (often done during any other visit)
Fit shuttered socket outlets£30–£60 per socket
Add supplementary bonding in bathroom£80–£200
Fit fire-rated downlight covers£10–£25 per downlight
Re-sleeve old cable ends at consumer unit£50–£100

Budgeting multiple C3 findings

A property with 4–6 C3 findings might have a total remedial cost of £300–£800. This is not urgent, but if the property is being sold or remortgaged, addressing C3 findings before a buyer’s solicitor asks questions can prevent delays. A seller’s solicitor requesting a copy of the EICR and finding C3 observations may prompt the buyer to request a price reduction.


FI — Further Investigation Required

What it means

The inspector could not fully assess a particular aspect of the installation. The code does not indicate severity — it indicates incompleteness. The investigation was stopped before a conclusion could be reached.

What faults produce an FI

FaultWhy it is FI (not C1/C2/C3)Example scenario
Wiring concealed in a wall where continuity could not be confirmedInspector could not test the cablecables buried behind plasterboard with no access
A circuit whose routing could not be tracedInspector could not determine what the cable feedsOld lighting circuit with unknown junction boxes
Evidence of a fault needing more detailed diagnosisInspector suspects a problem but cannot confirm without further workIntermittent RCD trips that did not occur during testing
Consumer unit internals inaccessibleInspector could not inspect connectionsSealed unit or excessive cable congestion
Underfloor heating cables — could not verify insulation resistanceTesting would require lifting the floorElectric mat system under tile

What happens with FI

Typical cost to resolve FI

FI scenarioTypical cost
Open up a junction box to test concealed wiring£80–£200
Trace an unknown circuit and label it£100–£250
Lift a section of flooring to test underfloor heating£200–£500
Extended fault-finding on intermittent RCD trips£150–£400

How Codes Appear on a Real EICR Report

An EICR report is structured into several sections. The codes appear in the Observations table:

┌─────────────────────────────────────────────────────────────────────┐
│  OBSERVATIONS                                                       │
├────┬──────┬─────────────────────────────────────────────────────────┤
│ #  │ Code │ Description                                            │
├────┼──────┼─────────────────────────────────────────────────────────┤
│ 1  │ C2   │ No RCD protection on the downstairs socket circuit.    │
│    │      │ Board is a 1980s split-load with no RCBOs.             │
├────┼──────┼─────────────────────────────────────────────────────────┤
│ 2  │ C2   │ Missing main bonding to the gas meter installation.   │
│    │      │ Gas pipe is metallic; no 10 mm² CPC visible.           │
├────┼──────┼─────────────────────────────────────────────────────────┤
│ 3  │ C3   │ Consumer unit labels are illegible. Circuit            │
│    │      │ identification is not possible at the board.            │
├────┼──────┼─────────────────────────────────────────────────────────┤
│ 4  │ C3   │ No supplementary bonding in the bathroom. RCD         │
│    │      │ protection is present; bonding is recommended only.     │
├────┼──────┼─────────────────────────────────────────────────────────┤
│ 5  │ FI   │ Downstairs lighting circuit routes behind the          │
│    │      │ kitchen plasterboard could not be confirmed.            │
└────┴──────┴─────────────────────────────────────────────────────────┘

OVERALL RESULT: Unsatisfactory (C2 findings present)

In this example:


Code Combinations and What They Mean

CombinationResultWhat happens
C1 onlyUnsatisfactoryImmediate isolation required. Remedial work before re-test.
C1 + C2UnsatisfactoryBoth must be fixed. C1 isolated immediately; C2 within 28 days (landlords).
C2 onlyUnsatisfactoryRemedial work required. New EICR after completion.
C2 + C3UnsatisfactoryC2 must be fixed (28 days for landlords). C3 recommended but not required.
C2 + FIUnsatisfactoryC2 must be fixed. FI must be investigated before the installation can be fully certified.
C3 onlySatisfactoryNo remedial work required. Address C3 findings when convenient.
C3 + FISatisfactory (with FI caveat)C3 findings are noted. FI must be investigated for a complete picture.
FI onlySatisfactory (incomplete)Inspector cannot fully certify. Investigation needed.
All clearSatisfactoryNo action needed. Re-inspect at the recommended interval.

The 28-Day Landlord Deadline

For landlords in England, Scotland, and Wales, the 28-day remedial deadline is one of the most important parts of the EICR process:

CodeLandlord deadlineHomeowner deadline
C1Immediate — isolate now; fix as soon as possible (often same day)No legal deadline; isolate immediately
C228 days from the date of the EICR (or shorter if the report specifies)No legal deadline; remedial work strongly recommended
C3No deadline — recommended improvementNo deadline
FINo deadline — investigation needed for a complete pictureNo deadline

Important: The 28-day clock starts on the date of the EICR, not the date you received the report. If the EICR was dated 1 June and you received it on 5 June, the deadline is 29 June.

Failure to comply with the 28-day deadline for C1/C2 findings can result in:


What Happens If You Ignore a C2

During the tenancy

The local authority can serve an improvement notice requiring remedial work within a specified period. Non-compliance with an improvement notice is a criminal offence — fine of up to £5,000, plus a daily fine of up to £500 for continued non-compliance.

At the next EICR

The same C2 finding will appear again at the next inspection (5 years for landlords), and may have worsened. A missing earth that was C2 in 2026 may become C1 in 2031 if the insulation degrades further.

When selling the property

The buyer’s solicitor will request the EICR. A C2 finding that has not been remediated will:

Insurance

If a fire or electrical incident occurs and the insurer discovers an unremediated C2 finding from a previous EICR, they can:


Remedial Work Process After a Failed EICR

  1. Review the observations — understand each C1/C2 finding
  2. Prioritise C1 findings — isolate immediately if not already done
  3. Get quotes — you can use any Part P-registered electrician, not necessarily the one who did the EICR
  4. Complete remedial work within 28 days (landlords) or as soon as practical (homeowners)
  5. Obtain an EIC (Electrical Installation Certificate) for any new work carried out
  6. Request a partial re-inspection — the original EICR inspector re-tests the affected circuits and issues a supplementary report confirming the C1/C2 findings have been resolved
  7. Update your records — file the EIC and supplementary report alongside the original EICR

📖 Related: Consumer Unit Upgrade: What to Expect When Replacing Your Fuse Board — upgrading a consumer unit is the most common remedial action after an Unsatisfactory EICR.


How Each Code Affects Property Sales

CodeImpact on saleWhat buyers look for
C1Cannot sell with C1 present — the installation is dangerous and a buyer’s solicitor will not proceedEICR showing no C1 findings
C2Significant obstacle — buyer will demand remedial work, price reduction, or will walk awayEICR showing no C2 findings (Satisfactory)
C3Minor friction — some buyers will request price reduction for C3 findings; most accept Satisfactory with C3Satisfactory EICR
FIIncomplete report — buyer may request the FI be investigated before proceedingComplete EICR with no outstanding FI

Best practice for sellers: Obtain an EICR at least 6 months before listing the property. Address any C1/C2 findings. A Satisfactory EICR with no C1/C2 findings and no FI is the cleanest outcome for conveyancing.


EICR Codes vs PAT Testing: Don’t Confuse Them

EICR codes (C1/C2/C3/FI) apply to the fixed installation — the wiring, consumer unit, and accessories. They are completely separate from PAT testing (Portable Appliance Testing), which tests movable equipment like kettles, toasters, and power tools.

PAT testing has its own pass/fail system — there are no C1/C2 codes. A failed PAT test means the specific appliance is unsafe, not the building’s wiring.

📖 Related: PAT Testing Explained: Portable Appliance Testing for Landlords and Businesses


Frequently Asked Questions

Can I remediate C2 findings myself?

Part P allows non-notifiable work to be carried out by a competent person. However, most C2 findings involve work on the consumer unit, new circuits, or work in special locations — all of which are notifiable under Part P. In practice, C2 remedial work must be carried out by a registered competent person or notified to Building Control.

How long is an EICR valid?

There is no fixed expiry date. The IET recommends 10 years for owner-occupied homes and 5 years for rented properties. The inspector specifies the re-inspection interval on the report.

Does a Satisfactory EICR mean my wiring is perfect?

No. A Satisfactory EICR means no C1 or C2 findings were found at the time of inspection. The installation may have C3 recommendations or may deteriorate over time. It is a snapshot, not a guarantee.

What is the difference between an EICR and an EIC?

An EICR is an inspection report assessing the condition of an existing installation. An EIC (Electrical Installation Certificate) is issued for new work — a new circuit, a consumer unit replacement, or any notifiable installation work. They serve different purposes.

Can I get a partial re-inspection instead of a full EICR?

Yes. If only specific circuits were affected by C1/C2 findings, the inspector can re-test just those circuits and issue a supplementary report. This is cheaper and faster than a full re-inspection.

What if my EICR has both C2 and FI findings?

The C2 must be remediated (28 days for landlords). The FI must also be investigated before the installation can be fully certified. Both need to be addressed, but the C2 has the legal deadline.


Quick Reference: EICR Code Summary

CodeNameDanger levelEICR resultLandlord deadlineTypical remedial cost
C1Danger PresentImmediate dangerUnsatisfactoryImmediate£50–£800
C2Potentially DangerousCould become dangerousUnsatisfactory28 days£100–£900
C3Improvement RecommendedNot dangerousSatisfactoryNo deadline£0–£800 total
FIFurther Investigation RequiredUnknownIncompleteNo deadline£80–£500

Simulate Faults in ElectraSim

ElectraSim lets you build circuits and inject the exact faults an EICR inspector looks for — so you can understand what each code means before receiving a report:

Reverse polarity (would be C1):

  1. Place a Power Supply, Switch, and Bulb
  2. Wire the switch into the neutral path
  3. Toggle the switch off — the bulb goes dark but the holder is still live
  4. This demonstrates why C1 exists: the holder is at 230 V even when the switch is off

Missing earth (would be C2):

  1. Add a Bulb connected to a Power Supply
  2. Remove the earth connection
  3. The circuit operates normally — the missing earth is invisible until a fault occurs
  4. Add an RCD and inject an earth fault — the RCD trips; without the RCD, the fault persists

Open ring (would be C2):

  1. Build a ring circuit with two paths from the distribution board
  2. Break one leg by removing a wire mid-loop
  3. All loads remain powered — the fault is invisible to normal operation but present in the wiring

🔍 ElectraSim’s simulation engine performs a full graph traversal on every circuit change — the same logical analysis an electrician applies during testing. Try it free →


Want to Understand Your EICR Better?

If you have received an EICR and are unsure what the codes mean, use ElectraSim to build a model of your own installation and explore each fault type. Understanding the why behind each code makes it easier to discuss remedial work with your electrician, prioritise spending, and avoid paying for unnecessary work. Open ElectraSim →

See It All in Action

Build and simulate the circuits from this article for free in your browser. No installation, no sign-up.

⚡ Open ElectraSim Free