Intermediate Guide

Cable Clipping and Containment: How to Run Electrical Cables Safely and Legally

📅 ✍️ ElectraSim ⏱ 18 min read

Choosing the right cable size gets most of the attention. How that cable is actually run through a building — how it is supported, protected, and routed — gets far less, yet it has an equally direct impact on safety, compliance, and the long-term integrity of the installation.

Run a cable through 100 mm of loft insulation without derating it and you have a fire risk. Clip it to a surface without adequate support and it sags, strains at terminations, and looks unprofessional. Bury it in a wall outside a prescribed zone without mechanical protection and you have created a concealed hazard that will catch the next person who drills in.

This guide covers every cable containment method used in UK domestic and light commercial wiring, the BS 7671 rules that govern each, and how to choose the right method for each situation.


Why Cable Containment Matters

Cable containment serves four distinct purposes:

  1. Mechanical protection — prevents physical damage from drilling, nailing, impact, or abrasion
  2. Thermal management — affects how much heat the cable can dissipate, directly impacting its current-carrying capacity
  3. Fire containment — limits the spread of fire through cable routes penetrating walls and floors
  4. Future identification — allows later occupants and electricians to find, trace, and work on cables safely

BS 7671 (the IET Wiring Regulations) addresses all four. Getting containment right means considering each purpose, not just picking whatever is easiest to install.


Surface Wiring: Clipping Cable Direct

The simplest containment method is clipping cable directly to a surface — wall, ceiling, or joist — using plastic cable clips.

How to clip cable correctly

Current rating for clipped cable

Cable clipped directly to a surface (or on a perforated cable tray) benefits from free air circulation on all sides — this is the reference installation method (Method C / Reference Method B in BS 7671 Table 4D5) and gives the highest current rating for a given cable size.

Cable SizeClipped Direct Rating (twin and earth, 70°C thermoplastic)
1.0 mm²14 A
1.5 mm²18.5 A
2.5 mm²24 A
4.0 mm²32 A
6.0 mm²41 A
10.0 mm²57 A

These ratings reduce when cables are grouped together, enclosed in insulation, or run in conduit. See Electrical Cable Sizes Explained for derating factors.

When surface clipping is appropriate

Surface clipping is the standard method for:

It is generally not appropriate as a finished installation in living areas — trunking or conduit provides a neater result and better mechanical protection.


Plastic Trunking

Trunking is a rectangular plastic channel with a removable lid, fixed to the surface, that encloses one or more cables in a neat run.

Types of trunking

TypeUse
Mini trunking (16×16 mm, 25×16 mm)Single cable runs — telephone, TV aerial, low-voltage data
Standard trunking (25×25 mm, 38×25 mm, 50×25 mm)Lighting and socket circuits in domestic installations
Dado trunkingMulti-compartment trunking at desk height — separates power, data, and comms
Skirting trunkingReplaces or covers the skirting board — conceals multiple circuits at low level
Floor trunkingRecessed into screeded floors for office power and data

Current rating in trunking

Cable enclosed in trunking runs warmer than cable clipped direct, because heat dissipation is reduced. BS 7671 requires a derating factor to be applied:

In practice, for domestic circuits where a single 2.5 mm² ring main cable runs in trunking, the 24 A clipped direct rating reduces to approximately 19 A in trunking — still well within the 32 A MCB protection, but the margin narrows. Always check grouping derating when multiple circuits share a trunking run.

Installing trunking correctly


Conduit

Conduit is a circular tube — plastic (PVC) or metal — through which cables are drawn after the conduit is fixed in place. Unlike trunking, individual cables (not twin and earth) are used inside conduit — typically singles in the appropriate colours.

Types of conduit

TypeMaterialUse
PVC oval conduitPlasticConcealed in plaster, dry lining — for a single cable run
PVC round conduitPlasticSurface or concealed, multiple cables, standard domestic and commercial
Flexible PVC conduitPlasticShort flexible sections at motors and equipment with movement
Steel conduit (heavy gauge)SteelIndustrial, high-mechanical-risk, or where the conduit itself is the earth path
Galvanised steel conduitSteelOutdoor and damp industrial environments

Advantages of conduit

Conduit fill — how many cables fit?

Conduit has a maximum fill ratio to allow cables to be drawn in and out without damage. BS 7671 Appendix 5 provides guidance:

Conduit SizeMaximum Number of 1.5 mm² singlesMaximum Number of 2.5 mm² singles
20 mm53
25 mm86
32 mm1410

Exceeding the fill ratio makes drawing cables impossible and risks damaging insulation during installation. Always design conduit runs with spare capacity.

Current rating in conduit

Cable in conduit (especially when conduit is concealed in thermal insulation) has significantly reduced current-carrying capacity. For 2.5 mm² singles in a 20 mm conduit concealed in a thermally insulated wall:

This is why conduit in thermally insulated walls requires careful cable sizing — see Electrical Cable Sizes Explained.


Concealed Wiring: The 50 mm Rule and Prescribed Zones

Concealing cables inside walls — in plaster, dry lining, or stud partitions — is the standard domestic wiring method. BS 7671 Regulation 522.6.6 and 522.6.7 set out the rules governing when and how this is permitted.

The 50 mm depth rule

A cable concealed in a wall or partition must be either:

  1. Within 50 mm of the surface (so it is in the zone where a future occupant would reasonably be expected to drill), AND protected by a 30 mA RCD, or
  2. Deeper than 50 mm, in which case it must have mechanical protection (steel conduit, steel trunking, or armoured cable) sufficient to prevent penetration by normal drilling and nailing, or
  3. In a prescribed zone (see below)

The logic: if a cable is within 50 mm of the surface and gets drilled through, the RCD trips immediately, protecting the person drilling. If it is deeper and has mechanical protection, the drill cannot reach it. Without either, a concealed cable is a hidden hazard.

Prescribed zones

A prescribed zone is an area of wall where cables are expected to run — and therefore where a reasonable person would check before drilling. BS 7671 defines prescribed zones as follows:

Vertical zones:

Horizontal zones:

Cables running inside prescribed zones without mechanical protection are acceptable because anyone drilling in these areas should reasonably expect cables to be present. Outside prescribed zones, a concealed cable either needs to be within 50 mm of the surface (with RCD protection) or have mechanical protection.

Visualising prescribed zones

┌─────────────────────────────────────────────────────┐
│░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░░│  ← Top zone (150 mm)
│                                                     │
│░░│                                           │░░░░░│  ← Corner zones (150 mm)
│  │         Safe drilling area                │     │
│  │         (no concealed cables              │     │
│░░│          without protection)              │░░░░░│
│                                                     │
│         [SOCKET]←150 mm→                           │
│░░░░░░░░░░░░░░░░                                     │  ← Horizontal zone from socket
└─────────────────────────────────────────────────────┘

The shaded areas are prescribed zones. Cables can run here without mechanical protection (subject to the 50 mm depth rule and RCD protection requirement). Outside these zones, cables must be in conduit, armoured, or buried at sufficient depth with mechanical protection.

Practical implications for DIY wiring

If you are running a new cable to a socket or switch:

  1. Plan the route through prescribed zones where possible — run up to the top of the wall, across within 150 mm of the ceiling, and back down to the new accessory location
  2. If the route must leave prescribed zones, use oval conduit or metal-clad conduit to protect the cable
  3. Always draw a sketch of where concealed cables run before plastering or dry lining — and photograph the run before covering it
  4. Ensure RCD protection on all circuits where cables are run within 50 mm of the surface

Armoured Cable (SWA)

Steel Wire Armoured (SWA) cable has a layer of steel wires wound around the insulated cores, providing a high level of mechanical protection. It is the correct choice for:

SWA cable installation

SWA vs twin and earth for outdoor runs

Do not use standard flat twin and earth cable for outdoor or underground runs — it is not rated for external use, is not UV-resistant, and has no mechanical protection. SWA (or suitable outdoor-rated flexible cable for short, above-ground runs with additional conduit protection) is the correct choice.

See How to Wire a Shed or Outbuilding for a complete guide to underground supply cables.


Cable Tray and Basket

Cable tray (solid or perforated steel or plastic tray) and cable basket (an open wire mesh structure) are used in commercial, industrial, and larger domestic installations to support multiple cables over long horizontal or vertical runs.

When to use cable tray

Current rating on perforated tray

Cables laid on perforated cable tray in free air have a current rating equivalent to clipped direct (or slightly higher for cables spaced apart), because air circulation is unrestricted. Cables touching on a tray must be derated for grouping.

Cable securing on tray

Cables must be secured to cable tray at regular intervals — typically every 300–500 mm on horizontal runs and every 150–300 mm on vertical runs — using cable ties or proprietary cable cleats. Unsecured cables on vertical tray runs can migrate under gravity, straining terminations.


Cable Runs Through Floors and Joists

Running cables through timber floor joists is standard practice in UK domestic wiring. BS 7671 and the Building Regulations both place requirements on how this is done.

Drilling joists — the rules

If you need to notch a joist (for larger cables or where drilling is not possible), notches must be in the outer quarter of the span and not deeper than 0.125× the joist depth.

Cables in floor voids

Cables suspended in a floor void (between ground floor joists, between ceiling and upper floor) are treated as clipped direct for current rating purposes if they are not lying on or embedded in thermal insulation.

If cables are clipped to the underside of floorboards and covered by loft insulation laid over them, derating for thermal insulation must be applied.

Penetrating fire-rated floors and walls

Any cable penetrating a fire-rated floor, ceiling, or wall must be fire-stopped at the penetration point. This means sealing around the cable with:

Failing to fire-stop cable penetrations is a serious building safety issue and a common EICR observation. It is also a Building Regulations compliance failure (Part B — Fire Safety).


Common Cable Containment Mistakes

Stapling through cables

Using a cable staple or hammer-in clip that has been driven through the cable rather than over it. This damages the insulation and creates a potential arc fault. Always use the correct size clip for the cable, and check that the clip sits over the cable, not through it.

Running cables across joists without protection

In accessible loft spaces, cables running across (not along) joists are vulnerable to foot traffic. They should be run through holes drilled in the joists, or protected by cable covers, not simply laid across the top.

Grouping circuits without derating

Running five ring main cables in a single trunking without applying grouping derating factors. The cables run hotter than rated, the insulation degrades faster, and the circuit may be undersized for its actual load. Check Electrical Cable Sizes Explained for derating tables.

Leaving cables outside prescribed zones without protection

Running a cable diagonally across a wall to save cable length — outside every prescribed zone — and then plastering over it. The next person to fit a picture hook, shelf bracket, or TV mount becomes a hazard. Always route through zones or use conduit.

Not photographing concealed cable routes

Covering a cable run without any record of where it is. A photograph with a scale reference (tape measure along the wall) before plastering costs nothing and can prevent a serious injury years later.

Incorrect SWA gland installation

Terminating an SWA cable without proper glands, leaving the armour unconnected to earth. The armour then provides no earth fault path and no protection — it is just a false sense of security.

Not fire-stopping penetrations

Passing conduit or trunking through a compartment wall and leaving the annular gap unsealed. A fire in one room can spread through the unsealed penetration in minutes.


Reference Method Summary

BS 7671 uses reference installation methods to determine current ratings. The method depends entirely on how the cable is installed:

Installation MethodBS 7671 ReferenceEffect on Current Rating
Clipped direct to surfaceMethod C (Ref B)Full rating — highest
In free air, touching a wallMethod B~90% of clipped direct
In conduit on a wallMethod C (enclosed)~80% of clipped direct
In conduit in a thermally insulated wallMethod B (insulated)~55% of clipped direct
Buried direct in groundMethod DDepends on soil, depth
In trunkingMethod B (enclosed)~80% of clipped direct
Touching in groups of 3Grouping factor 0.7070% of single-cable rating
Touching in groups of 6Grouping factor 0.5757% of single-cable rating

Always identify the worst-case section of a cable run — the section with the highest temperature rise or lowest heat dissipation — and size the cable for that section. A short section in insulation limits the entire circuit.


Quick Reference: Choosing the Right Containment Method

LocationRecommended Method
Living room / bedroom walls (finished)Oval conduit in plaster or prescribed zone cable, RCD protected
Kitchen / bathroom (tiled walls)Surface trunking or prescribed zone concealed cable
Garage / utility (exposed)Surface trunking or conduit
Loft — along joistsClipped direct or in oval conduit through joists
Loft — across joistsDrilled through joists or in conduit
Underground to outbuildingSWA cable, min 500 mm depth, marker tape
External wall (exposed)SWA or conduit (UV-rated, weatherproof fittings)
Through fire-rated floor/wallAny method + intumescent fire stopping at penetration
Commercial/industrial open runsPerforated cable tray or cable basket

Key Takeaways

Planning a new circuit? Use ElectraSim to design and verify your wiring layout before you pick up a drill — free, browser-based, no account required. Open ElectraSim →

See It All in Action

Build and simulate the circuits from this article for free in your browser. No installation, no sign-up.

⚡ Open ElectraSim Free